SE3015/SE3018 Multi-function Clamp Earth Resistance Tester
The SE3015/SE3018 Clamp Earth Resistance Tester features a 2.4-inch color display and a wide range of functions, supporting Clamp Resistance measurement, Three-Four-Wire resistance measurement, and simultaneous detection of AC voltage and AC current. The instrument includes data storage, data retrieval, alarm alerts, and an automatic shutdown function, meeting various grounding test and field measurement requirements.
Applications
Power operation and maintenance: Using three or four-wire resistors or clamp-on resistors for measurement, to test the resistance of
towers, lines, substations and grounding grids, ensuring power supply safety.
Communication Room: Measure the grounding resistance of the communication room and base station, and retain and recall the lightning protection test records through data storage.
Oil fields and gas stations: Test the explosion-proof grounding resistance and utilize the alarm function to promptly detect grounding hazards.
Industrial Equipment: During the installation and maintenance of mechanical and electrical systems, measure the grounding resistance of the equipment to ensure electrical safety.
Lightning protection facilities: Test the resistance of lightning rods and lightning nets, and use AC voltage/current measurements to assist in determining the status of the lines.
Meteorological station: Conduct on-site testing of grounding system in the field. Utilize shock-proof, dust-proof and moisture-proof structure to adapt to complex environments.
It can easily adapt to various environments and display clear readings even in dim light.
Equipped with a Check Ring to verify the accuracy of the instrument. Tightly closed without gap, reduce magnetic induction error.
Maximum 500 groups data can be stored to view and operate.
When the measured value exceeds the alarm set value, an alarm will be issued.
| SE3015 | SE3018 | |
| Measurement | ||
| Clamp Resistance Range | 0.00 Ω-1500 Ω | 0.00 Ω-1800 Ω |
| Leakage Current Range | 0.000 mA-40 A | 0.000 mA-50 A |
| Ground Voltage Range | 600 V | |
| Resistance Resolution | 0.01 Ω | |
| Current Resolution | 1 uA | |
| Voltage Resolution | 0.0 1V | |
| Three-Four-Wire method range | 0.00 Ω-3000 Ω | 0.00 Ω-30 kΩ |
| Soil Resistivity Range | ○ | 0.00 Ω-9999 kΩm |
| Function | Ground resistance test, loop resistance test, AC current test, AC voltage test | |
| Accuracy guaranteed temperature and humidity | 23℃±5℃, below 75%rh | |
| Measure Time | 1 time/s | |
| Data Storage | Maximum 500 groups of data | |
| Overflow Display | “OL” symbol indication when over-range overflow | |
| Automatic Shut-down | Turn off automatically after 15 minutes | |
| USB Data upload function | ● | |
| General Characteristics | ||
| Communication | USB | |
| Power | DC 3.7 V 750 mA Lithium battery | |
| Screen | 2.4 inch color LCD screen | |
| Dimention/Weight | 273mm×106mm×53mm/975g(including battery) | |
Instrument box
Charger
USB communication line
Check Ring
Simple test line
Auxiliary grounding rod
Test Line
CD